文章标题:喷淋降温系统常见故障及排查--Common faults and troubleshooting of spray cooling systems
添加时间:2024-05-07
点击次数:132
序号 Item |
常见故障表现 Common faults |
故障可能因素 Possible factors for faults |
解决方案 Solution |
1 |
个别喷头非正常喷水,或停止喷淋后个别喷头还在喷水 Some nozzles spray water abnormally, or some nozzles still spray water after stop spraying |
喷头内有异物 Foreign objects inside the nozzle |
清理喷头内异物 Clean foreign objects inside the nozzle |
2 |
喷淋启动后,其中一路喷水压力较小 After startup, one of the water spray pressures is relatively low |
过滤器滤网堵塞; 或管线堵塞。 Filter screen clogged; Or pipeline blocked |
定期清理过滤器; 检查清理管线 Regularly clean the filter; Inspect and clean the pipeline |
3 |
水泵启动后不停,压力数值达不到设定压力 The pump can not stop after startup, and the pressure cannot reach the set pressure. |
储水箱内水位过低; 水泵腔体可能进气 The water level in the water storage tank is too low; The water pump chamber may be filled with air. |
做好水源管理; 参见说明书,排出水泵内气体。 Properly manage the water sources; Refer to the manual and discharge the gas inside the water pump. |
4 |
环境温度未达到设定温度喷淋启动 The ambient temperature has not reached the set temperature, but the spray started |
温度未校准; 温度感应探头损坏 Temperature not calibrated; Temperature sensing probe damaged |
参见说明书,校准温度数值; 如果温度感应探头损坏,联系厂家更换。 Refer to the manual to calibrate the temperature values; If the temperature sensing probe is damaged, contact the manufacturer for replacement. |
5 |
环境温度超过设定温度,喷淋不启动。 Ambient temperature exceeds the set temperature, but the spray does not start. |
||
6 |
电磁阀不能正常打开 The solenoid valve cannot open normally |
控制箱中变压器损坏 The transformer in the control box is damaged |
测量控制箱是否有AC24V输出,如无输出,请联系厂家更换变压器。 Check if the control box has AC 24V output. If there is no output, please contact the manufacturer to replace the transformer |
电磁阀损坏 Solenoid valve damaged |
测量控制箱中是否有AC24V输出,如有输出,请联系厂家更换电磁阀(或电磁头)Measure if there is AC 24V output in the control box. If there is an output, please contact the manufacturer to replace the solenoid valve (or solenoid head) |